Contact
DYNATIME SA
Av. des Champs-Montants 12a
CH - 2074 Marin
For over 30 years, DYNATIME SA is a Swiss distributor of equipment for automation and industrial electronics.
Compact PID controller 32×74 mm
Universal input, NFC programming, RS485 option
The Pixsys ATR144 is a 32×74 mm PID controller that follows the standards of the Blue Line range. Its high-contrast white display remains readable in an industrial environment, and its scrolling assist function guides the operator directly on the front panel.
The analog input accepts thermocouples K, S, R, J, T, E, N and B, thermoresistors PT100, PT500, PT1000, Ni100 and Ni120, PTC and NTC thermistors, as well as process signals 0…10 V, 0/4…20 mA and 0…60 mV. Therefore, the same model covers most of the sensors in the existing fleet.
With the MyPixsys app (Android and iOS), the controller is configured from a smartphone via NFC, without wiring and without powering the device on. The settings are prepared in the workshop or duplicated in series in just a few seconds.
The ATR144-ABC version has 2 5 A relays. The ATR144-ABC-T version retains 1 relay and adds an isolated RS485 port in Modbus RTU to send the measurements to an automation or supervision system.
Despite its compact size, the ATR144 incorporates a dual hot/cold PID, soft-start, open/closed logic for motorized valves, and a loop break alarm.
DYNATIME SA distributes Pixsys controllers in Switzerland and helps you choose between versions with or without communication. You can also discover our complete range of products. temperature control, or contact us for technical advice or a quote.
| Dimensions | 74 x 32 x 53 mm |
|---|---|
| Nutrition | 24…230 VAC/DC ±10 %, 50/60 Hz (galvanic isolation 2.5 kV) |
| Consumption | 5 W/VA |
| Display | 4 white digits 0.38″ + 5 red digits 0.28″, 6 LEDs |
| Materials | Enclosure and front panel: UL94V2 self-extinguishing PC |
| Weight | Approximately 120 g |
| Protection index | Front view IP65, enclosure and terminals IP20 |
| Terms of use | 0 to 45 °C, 35 to 95 % RH, maximum altitude 2000 m |
| Certifications | CE, UL |
| Analog input | 1 input, resolution 16 bits |
|---|---|
| Thermocouples | K, S, R, J, T, E, N, B (cold welding compensation -25 to 85 °C) |
| Thermostatic resistances | PT100, PT500, PT1000, Ni100, Ni120, PTC 1K, NTC 10K, NTC 2252 |
| Process signals | 0…1/5/10 V (50,000 points), 0/4…20 mA (40,000 points), 0…60 mV (25,000 points) |
| Potentiometer | 1…150 kΩ (50,000 points) |
| Precision | ±0.2% full scale ±1 digit at 25 °C |
| Digital entries | 2 PNP (1 with PT100) |
| Sampling time | Programmable up to 2.1 ms (470 Hz) |
| ATR144-ABC | 1 analog input, 1 digital input, 2 5 A 250 VAC relay outputs |
|---|---|
| ATR144-ABC-T | 1 analog input, 1 digital input, 1 5 A 250 VAC relay, isolated RS485 (1200 to 115 200 baud) |
| SSR output | 1 output 12 VDC, 25 mA max. |
| Auxiliary output | 12 VDC, 30 mA max. for sensor power supply |
| Regulatory algorithms | ON/OFF with hysteresis, P, PI, PID, PD in proportional time |
|---|---|
| Adjustment | Manual or automatic (autotuning) |
| Alarm modes | Absolute/threshold, band, high/low range, manual reset and delay in activation optional, loop break alarm |
| Double PID | Hot/cold |
| Soft-start | Gradient in degrees/hour or fixed output percentage |
| Open/closed logic | For motorized valves |
| Configuration | NFC (app MyPixsys), micro USB and MyPixsysLab software, Memory Card, EASY-UP codes |
| Data protection | Locking of the settings, access to the parameters via password |
PID controller 72×72 mm
Up to 4 relay outputs, 24...230 V power supply
Touchscreen pedestals 4.3″ to 15″ with software automation
IEC 61131-3 programming, Ethernet, RS485, CAN
Converters for PT100, PT1000, Ni100 and thermocouples
Output 4…20 mA or 0…10 V, 16-bit conversion
Modbus, CANopen and Ethernet I/O systems, automation and HMIs
Modular platform, from a few points to thousands of I/O
PID controller for DIN rail, 4 modules
Universal input, isolated analog output, RS485 Modbus
PID controller 48×48 mm (1/16 DIN)
1 or 2 analog inputs, NFC programming, RS485 option